THIS IS OUR VERSION OF WHAT IS TYPICALLY SOUGHT AFTER TO SUCCESSFULLY PASS INSPECTION, SOME AHJ REQUIRE MORE, SOME LESS. WE LIKE TO KEEP OUR DATA-BASES MAINTAINED ACCORDINGLY.
PLACE ON MSP DEADFRONT DOOR
- H-PLQ-001 - DIRECTORY MAP; CEC 2019 705.10
- P/L-002 - DC DISCONNECT (RATING); CEC 2019 690.53
- P/L-003 - AC DISCONNECT (RATING); CEC 2019 690.52
- P/L-004 - DC DISCONNECT (ONLY)
- P/L-005 - AC DISCONNECT (ONLY)
- P/L-006 - POWER SOURCE OUTPUT; CEC 2019 705.12 (B)(2)(3)(B)
- P/L-008 - TERMINALS MAY BE ENERGIZED; CEC 2019 690.13(B)
- P/L-009 - DO NOT EXCEED BUSBAR; CEC 2019 705.12(B)(2)(3)(C)
- P/L-010 - GROUND FAULT; NEC 2020 690.35(F)
- P/L-014 - PV SYSTEM CONNECTED
- P/L-016 - DUAL POWER SOURCES; NEC 2020 705.12(B)(3)
- P/L-017 - DE-RATE WARNING - IF NEEDED
- P/L-025 - METER ADDITION
PLACE NEAR PV OCPD
PLACE NEAR MAIN BREAKER - IF NEEDED
- P/L-019 - DERATE 150
- P/L- 020 - DERATE 175
PLACE ON JUNCTION BOX(S)
- P/L-023 - J-BOX (DC)
- P/L-024 - J-BOX (AC)
PLACE ON COMBINER PANEL | BOX
- P/L-015 - DO NOT ADD LOADS; NEC 2020 690.33(E)(2)
PLACE NO LESS THAN 3' OF DISCONNECT; CEC 2019 690.56
- P/L-011 - RAPID SHUTDOWN (Y); FIG. 690.56(C)(1)(B)
- P/L-013 - RAPID SHUTDOWN SWITCH; CEC. 690.56(3)
PLACE ON CONDUIT EVERY 10-FEET, BEFORE & AFTER EVERY BEND; CEC 2019 690.31(G)(3)
- L-018-CAUTION SOLAR CIRCUIT LABELS